Combustion Air Systems CAS-4Jr.™ CAS-3 (Oil) and CAS-4 (Gas)
These models are designed to provide combustion air for appliances when direct connection to the burner is not possible (when the appliance is located in a confined space). According to NFPA 54 and NFPA 31, an engineered system such as a CAS-3, 4, 6 or 7 may be used to overcome the lack of air in a confined space. The CAS-3 is designed for use with oil appliances. The CAS-4 is for use with gas appliances with 24 VAC gas valve controls. The CAS-4MV is for use with 750mV power pile gas appliances. Each is designed for optimum safety and includes a proving device that won’t allow the burner to engage without the Fan-in-a-Can® operating. Multiple units or additional controls are required for multiple appliance installations. Each is equipped with a two speed control for enhanced versatility.
How the CAS-3 and CAS-4 work
When the thermostat calls for heat, the Fan-in-a-Can® engages and begins drawing air into the structure. When air flow is established, the pressure switch closes. The CAS sends a signal to the appliance, allowing the burner to fire. The Fan-in-a-Can® diffuses the outside air into the room near the burner to ensure adequate air for efficient combustion.
|
Model |
Fuel |
Application |
Appliance Input |
Components |
CAS-3 |
Oil |
Any oil heating appliance 120V |
See Installation Spec Chart below |
4" Intake Air Hood
Fan-in-a-Can®
6" to 4" Reducer
Restrictor Plate |
CAS-4 |
Gas |
24V Gas Appliance |
See Installation Spec Chart below |
4" Intake Air Hood
Fan-in-a-Can®
6" to 4" Reducer
Restrictor Plate |
CAS-4MV |
Gas |
750mV Power Pile Gas Appliance |
See Installation Spec Chart below |
4" Intake Air Hood
Fan-in-a-Can®
6" to 4" Reducer
Restrictor Plate |
CAS-4P |
Gas |
Boiler with automatic vent damper |
See Installation Spec Chart below |
4" Intake Air Hood
Fan-in-a-Can®
6" to 4" Reducer
Restrictor Plate
ADA-1 |
For multiple appliances, the following additional controls should be used.
Model |
Description |
CK-20FV/FG |
Additional 30mV gas water heater control for use with CAS-4 and CAS-4Jr. |
CAC-24 |
Additional 24 Volt appliance for use with CAS-4, CAS-4Jr., CAS-6, and CAS-7 |
CAC-120 |
Additional 120 Volt appliance for use with CAS-3, CAS-6, and CAS-7 |
CAS-4Jr. |
|
 |
Installation Specifications
Total Input of Appliance(s) |
Max. Equivalent Feet of Installation |
CAS-3 OIL |
CAS-4, 4mV, 4P GAS |
4" duct & hood w/ Restrictor |
4" duct & 4" hood |
6" duct & 6" hood |
(gph) |
(BTU/hr) |
HI |
LOW |
HI |
LOW |
HI |
LOW |
- |
50,000 |
300 |
300 |
300 |
300 |
300 |
300 |
.50 |
75,000 |
300 |
300 |
300 |
300 |
300 |
300 |
.75 |
100,000 |
300 |
300 |
300 |
300 |
300 |
300 |
.90 |
125,000 |
300 |
220 |
300 |
220 |
300 |
300 |
1.00 |
150,000 |
174 |
108 |
232 |
118 |
300 |
300 |
1.25 |
175,000 |
99 |
48 |
152 |
63 |
300 |
300 |
1.35 |
200,000 |
52 |
14 |
102 |
32 |
300 |
300 |
1.55 |
225,000 |
20 |
NA |
68 |
13 |
300 |
239 |
1.75 |
250,000 |
NA |
NA |
45 |
NA |
300 |
150 |
2.00 |
300,000 |
NA |
NA |
16 |
NA |
300 |
53 |
2.50 |
350,000 |
NA |
NA |
NA |
NA |
193 |
8 |
2.75 |
400,000 |
NA |
NA |
NA |
NA |
109 |
NA |
3.25 |
450,000 |
NA |
NA |
NA |
NA |
56 |
NA |
CAS-4Jr.™
The Fan-in-a-Can, Jr. is designed for gas appliances up to 110,000 BTU/hr input. A 4” intake Air Hood (IAH) is included along with mounting brackets to secure the Fan-in-a-Can, Jr. to a wall. It may be used with a residential water heater with the addition of control kit CK-20 FV/FG.
Total Input of Appliance(s) |
Maximum Equivalent Feet of Duct Pipe |
BTU/hr |
4" Pipe |
5" Pipe |
6" Pipe |
50,000 |
230 |
300 |
300 |
60,000 |
160 |
300 |
300 |
70,000 |
105 |
300 |
300 |
80,000 |
70 |
214 |
300 |
90,000 |
40 |
122 |
300 |
100,000 |
25 |
76 |
180 |
110,000 |
15 |
46 |
80 |
|